Air Quality Display

  • Model No.:AQD-100-SD
  • Made in:Taiwan, ROC
Add to favorites

Contact Us

Key Features

AQD series displays three most crucial parameters of IAQ; CO2 level, humidity and temperature. It also provides
date, day and time. It uses good quality sensors; such as the NDIR CO2 sensor, temperature and humidity sensors
which are usually available only in laboratory air quality diagnostic equipment. AQD series measures CO2
concentration which may not be noticeable by us and used the reading to control ventilation so that the indoor CO2
level can be kept below the recommended ASHRAE limit of 1000ppm. Monitoring humidity is very important as
extended period in an area with humidity over 60% or below 40% can create conditions for mold and mildew growth
that may cause allergies and affect general health.
 

Specifications

 General
 Type  Wall mount
 Parameters  CO2, Relative Humidity, Temperature
 Operating Environment  -10 ~ 60 ℃ / 0 ~ 95%RH, non-condensing
 Storage temperature  -10 ~ 60 ℃
 Clock  Real time clock with battery backup
 Power supply  12 VDC (supply with an AC adapter 100~240V / 50~60Hz )
 Current consumption  1.2A (max)
 Display  7 segment LED display
 Memory capacity  60000 values
 CO2 Measurement
 Measurement principle  Non-dispersive infrared (NDIR) with automatic calibration
 Measurement range  0 ~ 9999 ppm
 Accuracy tolerance  0 ~ 2000ppm ±3% and ±40 ppm note1 and 2
 Response time  2 minutes by 90%
 Maintenance  Maintenance-free for normal indoor applications
 Environmental  -10 ~ 60 ℃/ 0 ~ 95%RH, non-condensation
 Display digit  4 digits, 0 ~ 9999
 Relay setting  1200ppm
 Hysteresis  100ppm
 Humidity Measurement
 Measurement range  0 ~ 95 %RH
 Accuracy tolerance  ± 3 %RH (typical)                                                    
 Repeatability  ± 0.1 %RH
 Response time τ63  < 8 s (τ63%, 25℃)
 Long-term drift  < 0.5 %RH / year
 Display digit  2 digits, 0 ~ 99
 Relay setting  70%RH
 Hysteresis  5%RH
 Temperature Measurement
 Measurement range  -10 ~ 60 ℃             
 Accuracy tolerance  ± 0.3 ℃ (typical)
 Repeatability  ± 0.1 ℃
 Response time τ63  5~30 s (τ63%, 25℃)
 Long-term drift  < 0.04 ℃/ year
 Display digit  3 digits (One decimal point), 0.0 ~ 99.9                   
 Relay setting  28℃
 Hysteresis  1℃
 Outputs
 RS-485    RS485 (Modbus RTU)
 Relay  3 Relay outputs for CO2, relative humidity, and temperature respectively.N.O. and N.C. (2A/30VDC)
 Mechanical
 Housing material  PMMA panel (4mm), SPCC casing (1mm) 
 Dimensions  527 x 217 x 32 mm
 Weight  2600g
 
Note 1: In normal IAQ applications. Accuracy is defined after minimum 3 weeks of continuous operation with ABC. However, some industrial
applications do require maintenance.℃
Note 2: Accuracy is specified at room temperature +25°C and at normal pressure 101.3 kPa. Specification is referenced to certified calibration
mixtures. Uncertainty of calibration gas mixtures (+-1% currently) is to be added to the specified accuracy for absolute measurements.